4.4 System Operation (Main Menu Options)
Pressing the [Shift] key from the normal display will open the Main Menu on the alphanumeric display. The first option,
1) Commission, is not available to Control Level 2 Operators. See the Analog Fire Alarm Control Panels Programming
Guide (P/N: 38789) for commissioning and programming information. The other options on the Main Menu permit tests
and the setting, enabling and disabling of various system functions.
[ACTIVE] 1) Commission 2) Test 3) Time [1]
4) Enable 5) Disable 6) Print 7) View
Figure 7: Main Menu
4.4.1 System Tests
Select 2) Test from the Main Menu to open the Test Menu. This menu allows the Control Level 2 user to test the
following:
• The LEDs on the Front Panel Display
• The alphanumeric (liquid crystal) display
• Detection and alarm initiating devices connected to the polling circuit
• NAC and other alarm condition devices connected to the system
1) LEDs 2) LCD 3) Zones 4) Outputs
Figure 8: Test Menu
Note: If no action is taken, the display reverts to the normal display after one minute.
Note: The fourth option in the Test Menu, 4) Outputs, is not available to Control Level 2 Operators.
4.4.1.1 LEDs Test
Select 1) LEDs by pressing the [1] key. The panel will flash all LEDs on the LED display and step through all the alarm
and trouble LEDs in the Zone/Area display. On completion of the test, the display will report the results of the test and
automatically revert back to the normal menu after one minute. To interrupt and end the test, press the [No] key.
4.4.1.2 LCD Test
Select 2) LCD from the Main Menu by pressing the [2] key. The alphanumeric display will flash all characters in all
spaces on the alphanumeric display and return to the Main Menu.
4.4.1.3 Zones Test
Select 3) Zones by pressing the [3] key. The Zones Test allows the operator to test devices on the polling circuit(s) and
peripheral device circuit(s) without having to reset the panel after each device is tested.
Note: If no action is taken within one minute, the display reverts to the normal display. Press the [>] key to restore the Test
display.
The panel displays Zone Test Menu 1.
Ring bells?
Figure 9: Zone Test Menu 1
Press the [Yes] key to activate the NAC devices briefly as each device is tested, or press the [No] key to bypass the
indicator test. The panel then displays Zone Test Menu 2.
Control Level 2
Komentarze do niniejszej Instrukcji