  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 5
C-0636-030-040
D636A COMMAND CENTER
I
BLACK
RED
Figure 5: INSTALLING THE
D636A
COMMAND CENTER TO THE
D6112
D636A
COMMAND CENTER
&
/
WHITE
WHITE
RED
BLACK
Figure 6: INSTALLING THE D636A COMMAND CENTER TO THE D4112
9.1
Remove the Front Cover
-
Remove the front
cover from the enclosure base. Use a small
flat-
bladed screwdriver to gently push the two bottom
cover tabs back. As the tabs are pushed back, lift
the bottom of the cover away from the base.
Remove the cover.
9.2
Wire the
D636A
-
The total cable length used to
connect the command centers to the Control/
Communicator can run no longer than 1000 feet
when using 22 AWG. The wire run between serial
devices (D420, D620, D626, D630,
D636A
or
D640) can be no
more
than
300 feet. Route the
four color-coded flying leads through the wiring
opening in the back of the enclosure base and plug
intotheserialdatawirtngconnectorinthecommand
center. Figures 5 and 6 show typical installations
using one
D636A
command center. For installing
more than one device refer to the
D6112 Operation
and
installation Manual (74-04366-000) or the
D4112
Installation and Programming Manual (74-
05365-000).